H05Z1-K / H07Z1-K

Halogen free fitting wire

H05Z1-K / H07Z1-K

Halogen free fitting wire

Use

The fitting wire is used at electrical systems or other places where it is required to have a halogen free wire.

Construction

Conductor:

Copper, Cl. 5, Stranded

Isolation:

Halogen free compound LSZH TI7, in different colours

Technical data

Rated voltage:

H05Z1-K: 300/500 V

H07Z1-K: 450/750 V

Test voltage:

H05Z1-K: 2 kV

H07Z1-K: 2,5 kV

Temperature:

Max. operating temperature: 70°C

Min. operating temperature: -10°C

(without mechanical shocks)

Minimum installation temperature: 5°C

Short circuit 5 s

+160° C

Standards

H05Z1-K:

BS EN 50525-3-31

BS EN 60332-1-2

BS EN 50267-2-1

BS EN 50267-2-2

BS EN 60684-2

IEC 60684-2

BS EN 61034-2

Low Voltage Directive: 2014/35/EU

RoHS Directive: 2011/65/EC

 

 

H07Z1-K:

BS EN 50525-3-31

BS EN 60332-3-24

(CEI 20-22 III)

BS EN 60332-1-2

BS EN 50267-2-1

BS EN 50267-2-2

BS EN 60684-2

IEC 60684-2

BS EN 61034-2

Low Voltage Directive: 2014/35/EU

RoHS Directive: 2011/65/EC